October 30, 2022 - Everett Marina

October 30,  2022 - Everett Marina

Over the weekend, while performing minor maintenance actions, one row of our electrical panel went dark.  A quick consultation with the schematics illustrated that the dark row is powered through a 100 amp breaker shared with an adjacent row.  Given that one row was powered, it was suspected that there was a loose connection between the two rows.

Carefully opening up the back of the electrical panel the connecting bridge between the two rows was spotted.  Tightening the screws restored power to the dark row however it could be seen that there was a tapered gap on the one leg of the bridge raising question about the robustness of the connection.

The 3/16" thick copper bar was removed and inspected and it could be seen that the connecting legs were not parallel resulting in the gap.  A minor adjustment of the leg was made and a much better connection established.



Electrical schematic illustrating the left two rows share a common connection to the 100 amp breaker



Removed bus bar connecting the two rows


Comments

Popular posts from this blog

January 11, 2023 - Van Isles, BC - On the hard

August 25, 2025 - Everett

August 18, 2025 - Gowland Harbour